Parameters AC resistance, DC voltage
Accuracy Resistance: 0.5%±5dgt
Voltage: 0.05%±5dgt
Measurement Range Resistance: 0.001m?~3.3000?
V: 0.0001V~200.00V
Signal Source AC: 1kHz Open-circuit Voltage: <; 30mv Current: <; 15mA
Range Automatic, Manual, Nominal with 6 ranges
Speed 20 times/second, 10 times/second, 3 times/second
Result Display ABS/PER/SEQ
Max Reading Resistance: 3200 Voltage: 5000
Max Resolution Resistance: 0.01m? Voltage: 1mV
Adjustment Short-circuit reset for each range
Comparator Voltage compare separately, resistance compare separately,
Voltage and resistance combination compare GD/NG sorting result display, beep
Trigger Internal, Manual, Remote
Test Terminal 4 terminal shielding ( 2 check terminal and 2 driving terminal) and external shielding ground section
Configuration Interface Build-in Mini-USB (virtual serial port); Charging Interface; U disc Interface
Others 3.5 inches true color 16M color TFT-LCD display
Keypad lock and data hold function
Compatible SCPI Order Set
Switch in both Chinese and English
Adjustable Background light Auto power-off
Adaptor(ATL909) Input: 100-240V~50/60Hz 0.35A Output: 9V 1A DC
Battery Parameters 8.4v, Li, 2200mAh rechargeable battery
Charging Time Single continued charging time: max 300 Min
Working Life ? 8 hours
Dimension & Weight 130.23mm (Width)*210.76mm (Height)*37.88mm (Depth) 650g
Please confirm the model number before purchase.
If you have any questions about the product, please contact us.
True color 3.5 inch LCD display in English, more convenient operation.
Online test of UPS battery, basic accuracy
Resistance: 0.5% Voltage: 0.01% Resistance: 0.001m? ~ 3.3000? Voltage 0.0001V~200.000VDC
Five-range automatic and manual test speed 145 times / sec, 30 times / sec, 10 times / sec, 1 time / sec
Maximum reading resistance: 33,0000 Voltage: 200,000